Holtop Suspended AHU Air Handling Unit with Heat Recovery

Holtop is a factory providing Suspended AHU Air Handling Units with Heat Recovery. Our top-quality products are designed to improve air quality and save energy. Contact us today for a quote! #airhandlingunits #heatrecovery #factory #sustainability

Request a Quote
  • Holtop Suspended AHU Air Handling Unit with Heat Recovery

PRODUCTS DETAILS

MAIN FEATURES AND COMPONENTS

Main features: • Equipped with supply fan and exhaust fan, brings in the fresh air and exhausts out stale indoor air as well. • Equipped with plate heat exchanger, recovers energy from outgoing indoor air, to save operating costs. • Thin height, easily installed in the ceiling space.  rooftop ahu Housing construction a. Double skin panel 25mm thick, inner skin made of galvanized steel sheet, outer skin color steel sheet, between skins is sandwiched with high-density fireproof PU with a thermal coefficient below 0.0199W/m∙˚C b. High airtightness Double inlaid sealing system to tightly join the framework and panels, total air leakage rate below 3% panel Supply fan and exhaust fan Outer rotor motor, direct driven centrifugal fan, dynamic balance, compact and low noise level. fan Heat exchangers
  • Total heat or sensible heat type available for different applications. The total heat exchanger is made of special fiber paper, featured by high moisture permeability, good airtightness, excellent tear resistance, and aging resistance. Suitable for high humidity difference between conditioned space and outdoors.
  • The sensible heat exchanger is made of thin aluminum foil, featured by high heat conductivity and long service life. Suitable for the high-temperature difference between indoors and outdoors.
heat exchanger Airflow damper (optional)
  • The edges of the lamina are with special plastic seals, which ensures low leakage.
  • Manual or motorized control is available for options.
damper Water cooling/heating coil
  • Copper pipe with double-side bent wave hydrophilic aluminum foil, higher heat exchange performance.
  • Air releaser and drainage plug are set in pipe connection box to ensure return path free from accumulated air, convenient for maintenance in winter.
coil Filter
  • Plate type(G2) coarse filter as standard configuration (Medium filter F5~F8 available as per request of the customer)
  • Draw-push installation, easy maintenance.
filter

ELECTRICAL CONTROL

Standardly, we do not offer control boxes and related control components for AHUs but offer wiring terminals only. Besides, we offer the following control system as options. • Independent run/stop of supply fan and exhaust fan • Water switch control and temperature control • LCD thermostat controller • DDC (PLC) controller is optional control

SUITABLE AIRFLOW

Model Suitable airflow
HJK-010RQC~HJK-015RQC 1000m3/h~1500m3/h
HJK-020RQC~HJK-025RQC 2000m3/h~2500m3/h
HJK-030RQC~HJK-040RQC 3000m3/h~4000m3/h
HJK-050RQC~HJK-060RQC 5000m3/h~6000m3/h
HJK-080RQC~HJK-100RQC 8000m3/h~10000m3/h
PERFORMANCE PARAMETERS Parameter charts (fresh air condition)
Model L*W*H (mm) Rated airflow (m3/h) Supply fan Exhaust fan Coil Heat recovery efficiency (%) Filter class N.W. (Kg)
Input power (kw) ESP (Pa) Input power (kw) ESP (Pa) Rows Cooling cap. (kw) Heating cap. (kw) Water inlet/ out pipe spec.
HJK- 010RQC4DY1 2084*1120*550 1000 0.25 155 0.25 180 4 12.2 13.1 DN32 60 G2 240
HJK- 015RQC4DY1 2084*1200*570 1500 0.32 155 0.25 180 4 18.4 19.8 DN32 60 G2 260
HJK- 020RQC4DY1 2194*1280*570 2000 0.45 160 0.32 190 4 25.2 27 DN40 60 G2 280
HJK- 025RQC4DY1 2244*1400*620 2500 0.55 160 0.55 190 4 30.4 33.1 DN40 60 G2 310
HJK- 030RQC4DY1 2354*1400*630 3000 1 250 1 250 4 36.4 39.7 DN40 60 G2 360
HJK- 040RQC4DY1 2404*1400*695 4000 1 290 1 330 4 14.9 46.4 DN50 60 G2 400
HJK- 050RQC4DY1 2554*1530*705 5000 1.5 330 1.5 350 4 50.2 56.7 DN50 60 G2 440
HJK- 060RQC4DY1 2634*1750*800 6000 2.2 400 1.5 400 2 66 68.3 DN65 60 G2 530
HJK- 080RQC4DY1 2904*2000*900 8000 3 430 3 430 2 83.9 86.4 DN65 60 G2 690
HJK- 100RQC4DY1 2904*2200*960 10000 4 500 4 500 2 108.5 110.4 DN65 60 G2 770
Working Conditions: • Cooling: Outdoor air DB35˚C, WD28˚C, cold water inlet/outlet temperature 7˚C/12˚C. • Heating: Outdoor air DB0˚C, hot water inlet/outlet temperature 60˚C/50˚C.

Hot Products

Heat Wheels (Rotary Heat Exchangers)

Heat Wheels (Rotary Heat Exchangers)

Wall Mounted Series Wall Mounted ERV Energy Recovery Ventilation ( With CO2 Sensor Version)

Wall Mounted Series Wall Mounted ERV Energy Recovery Ventilation ( With CO2 Sensor Version)

Slim Series Residential Energy Recovery Ventilation System (ERVs 200~400 m3/h,AC motor)

Slim Series Residential Energy Recovery Ventilation System (ERVs 200~400 m3/h,AC motor)

Holtop AHU Modular Air Cooled Chiller(Heat Pump)

Holtop AHU Modular Air Cooled Chiller(Heat Pump)

AC Motor THC Series Commercial Energy Recovery Ventilators (ERVs 1500-2600 m3/h)

AC Motor THC Series Commercial Energy Recovery Ventilators (ERVs 1500-2600 m3/h)

Floor Standing Series Vertical Energy Recovery Ventilation (Ductless ERV 300~600 m3/h)

Floor Standing Series Vertical Energy Recovery Ventilation (Ductless ERV 300~600 m3/h)

Optional Parts- CO2 Sensor

Optional Parts- CO2 Sensor

TG Series Commercial Suspended Energy Recovery Ventilatation (ERVs 1500~3000 m3/h)

TG Series Commercial Suspended Energy Recovery Ventilatation (ERVs 1500~3000 m3/h)

DC Motor THC Series Commercial Suspended Energy Recovery Ventilation System (ERVs 600~1300 m3/h)

DC Motor THC Series Commercial Suspended Energy Recovery Ventilation System (ERVs 600~1300 m3/h)

Holtop Condensing Exhaust Heat Recovery Air handling Units

Holtop Condensing Exhaust Heat Recovery Air handling Units

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours